Customization: | Available |
---|---|
Warranty: | 18 Months |
OEM/ODM Service: | Yes |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Design Features
Class A compliance under international standards
Basic voltage measurement accuracy of±0.1%
Special waveform record function
200kS/s sample rate
Support multi language
32GB micro SD card
GPS time synchronization
Product Shows
Channel(Voltage/Current) | 4/4 | |||
Voltage Range | 1-1000Vrms, 6000V transient voltage | |||
Current Range | depends on supplied current clamp | |||
PC software analysis | Yes | |||
Micro SD card(bulid-in) | 32GB | |||
Battery | Lithium ion, 5200mAh/>8h | |||
Time Synchronization | GPS/Beidou(option) | |||
interface | USB Host, LAN, WIFI | |||
WIFI App | (option) | |||
Screen | 5.6' TFT LCD with resolution640*480(SA2200) | |||
Language | 14-Chinese, English, French, German, Italian, Japanese, Korean, Polish, Portuguese(Brazil/Portugal), Russian, Spanish (Latin/Spain), Turkish | |||
Dimension/Weight | 270*190*66mm/2.0kg | |||
Wire Combinatios | 1Ø+NEUTRAL,1Ø SPLIT PHASE,1Ø IT NO NEUTRAL,3Ø WYE, 3Ø DELTA, 3Ø IT, 3Ø HIGH LEG, 3Ø OPEN LEG, 2-ELEMENT, 2 1/2-ELEMENT |
|||
Electrical Safety | IEC61010-1 ,Safety Degree: 600V CAT IV 1000V CAT III | |||
Measurement | ||||
Voltage/Current/Frequency | Measurement Range | Resolution | Accuracy | |
Vrms(AC+DC) | 1 ~ 120Vrms | 0.001Vrms | ±0.1% of nominal voltage | |
120Vrms~400Vrms | 0.01Vrms | |||
400Vrms~1000Vrms | 0.1Vrms | |||
Vpk | 1 ~ 1400Vpk | 0.01Vpk | ±0.5% of nominal voltage | |
V(Crest Factor) | 1.0 ~ >2.8 | 0.01 | ±5% | |
Arms(AC) | 10mV/A | 0~150A | 0.01A | ±0.1%±0.1A |
1mV/A | 1~2000A | 0.01A | ±0.1%±0.1A | |
65mV/1000A | 10~6000A | 0.01A | ±0.1%±0.2A | |
A(Crest Factor) | 1 ~ 10 | 0.01 | ±5% | |
Frequency | 42.5~57.5(50Hz nominal) | 0.01Hz | ±0.01Hz | |
51~69(60Hz nominal) | 0.01Hz | ±0.01Hz | ||
320~480(400Hz nominal) | 0.01Hz | ±0.01Hz | ||
Dips & Swells | ||||
Vrms1/2 | 0 ~ 200% of nominal voltage | 0.01Vrms | ±0.2% | |
Arms1/2 | depends on current clamps | 0.01A | ±1% | |
Harmonic (IEC61000-4-7) | ||||
Harmonic Number | 1 ~ 100(50/60Hz) (IEC61000-4-7) 1~12(400Hz) | |||
Harmonic Voltage %f | 0.0 ~ 100.0% | 0.01% | ±0.1% ± nx0.1% | |
Harmonic Current %f | 0.0 ~ 100.0% | 0.01% | ±0.1% ± nx0.1% | |
THD | 0.0 ~ 100.0% | 0.01% | ±2.5% | |
Phase | -180° ~180° | 0.1° | ± nx0.1° | |
Power and Energy | ||||
P, S, Q1 | Max. 6000MW | 0.1kW | ±1%±10 digits | |
PF & cosФ | 0 ~ 1 | 0.01 | ±0.01 | |
kWh, kVAh, kvarh | depends on nominal voltage and current clamps | ±1%±10 digits | ||
Flicker (IEC61000-4-15) | ||||
Pst(10min)/Plt (2 hrs) | 0.00 ~ 20.00 | 0.01 | ±5% | |
Unbalance | ||||
Voltage | 0.0 ~ 20.0% | 0.10% | ±0.1% | |
Current | 0.0 ~ 20.0% | 0.10% | ±1% | |
Voltage Phase | -360° ~ 0° | 0.1° | ±0.1° | |
Current Phase | -360° ~ 0° | 0.1° | ±0.5° | |
Voltage Transient | ||||
Vpk | ±6000Vpk | 0.01V | ±15% | |
Vrms | 10 ~ 1000Vrms | 0.01V | ±2.5% | |
Min. Test Time | 5us | |||
Inrush Current | ||||
Arms | depends on current clamps | 0.01A | ±1% ± 5digits | |
Inrush Duration | 1 ~ 32min selectable | 10ms | ±20ms | |
Mains Signaling | ||||
Signaling Frequency | 60-3000Hz | 0.1Hz | ||
Relative V% | 0%-100% | 0.10% | ±0.4% | |
Absolute V3s (3s average) | 0.0-1000V | 0.1V | ±5% of Nominal voltage | |
Logger | ||||
Recording | user-defined parameters for 4 phases at the same time | |||
Memory | Data stored in Micro SD card, 32GB | |||
Duration Time | 2 hrs to 1 year, depends on the recording items and time interval | |||
Interval | 1s to 60 minutes | |||
Monitor | ||||
Support EN50160 in default or user-defined standard |