  • SA2200 Power Quality Analyzer Class a
  • SA2200 Power Quality Analyzer Class a
  • SA2200 Power Quality Analyzer Class a
  • SA2200 Power Quality Analyzer Class a
  • SA2200 Power Quality Analyzer Class a
  • SA2200 Power Quality Analyzer Class a
Find Similar Products

Basic Info.

Model NO.
SA2200
WiFi
Yes
Voltage Measuring
1-1000vrms
Current Measuring
Max 6000A(Depends on Current Clamps)
Dips & Swells
Yes
Harmonic
Yes
Power & Energy
Yes
Flicker
Yes
Unbalance
Yes
Voltage Transient
Yes
Inrush Current
Yes
Logger
Yes
Monitor
Yes
Transport Package
Carton
Specification
270*190*66 mm
Trademark
Suin
Origin
China
HS Code
90303900
Production Capacity
30000 Set/Year

Product Description

Overview

The critical importance of electrical power in today's society necessitates daily maintenance and management to ensure that problem's don't occur. When they do, for example due to an equipment failure or abrupt surge in demand, engineers face the need to analyze the cause quickly.

The Suin SA2100 and SA2200 help troubleshoot power quality problems in three- and single-phase power distribution systems. Especially the SA2200 can conduct tests according to the international IEC 61000-4-30 Class A standard.


Design Features

Class A compliance under international standards

Basic voltage measurement accuracy of±0.1%

Special waveform record function

200kS/s sample rate

Support multi language

32GB micro SD card

GPS time synchronization

Advance function interface

1. Track harmonics up to 100th

SA2200 Power Quality Analyzer Class a

2. Phase Diagram

SA2200 Power Quality Analyzer Class a3. Powerful logger function

SA2200 Power Quality Analyzer Class a4. Data analyze in PC software

SA2200 Power Quality Analyzer Class a
Product Shows

SA2200 Power Quality Analyzer Class a
SA2200 Power Quality Analyzer Class a
SA2200 Power Quality Analyzer Class a

Application

SA2200 Power Quality Analyzer Class a
SA2200 Power Quality Analyzer Class a
SA2200 Power Quality Analyzer Class a

Package Shows

SA2200 Power Quality Analyzer Class aSpecification
                                                                                                                Standard compliance:IEC61000-4-30 Class A

Channel(Voltage/Current) 4/4
Voltage Range 1-1000Vrms, 6000V transient voltage
Current Range depends on supplied current clamp
PC software analysis Yes
Micro SD card(bulid-in) 32GB
Battery Lithium ion, 5200mAh/>8h
Time Synchronization GPS/Beidou(option)
interface USB Host, LAN, WIFI
WIFI App (option)
Screen 5.6' TFT LCD with resolution640*480(SA2200)
Language 14-Chinese, English, French, German, Italian, Japanese, Korean, Polish, Portuguese(Brazil/Portugal), Russian, Spanish (Latin/Spain), Turkish
Dimension/Weight 270*190*66mm/2.0kg
Wire Combinatios   1Ø+NEUTRAL,1Ø SPLIT PHASE,1Ø IT NO NEUTRAL,3Ø WYE,
3Ø DELTA, 3Ø IT, 3Ø HIGH LEG, 3Ø OPEN LEG,
2-ELEMENT, 2 1/2-ELEMENT
Electrical Safety IEC61010-1 ,Safety Degree: 600V CAT IV 1000V CAT III
Measurement
Voltage/Current/Frequency Measurement Range Resolution Accuracy
Vrms(AC+DC) 1 ~ 120Vrms 0.001Vrms ±0.1% of nominal voltage
120Vrms~400Vrms 0.01Vrms
400Vrms~1000Vrms 0.1Vrms
Vpk 1 ~ 1400Vpk 0.01Vpk ±0.5% of nominal voltage
V(Crest Factor) 1.0 ~ >2.8 0.01 ±5%
Arms(AC) 10mV/A 0~150A 0.01A ±0.1%±0.1A
1mV/A 1~2000A 0.01A ±0.1%±0.1A
65mV/1000A 10~6000A 0.01A ±0.1%±0.2A
A(Crest Factor) 1 ~ 10 0.01 ±5%
Frequency 42.5~57.5(50Hz nominal) 0.01Hz ±0.01Hz
51~69(60Hz nominal) 0.01Hz ±0.01Hz
320~480(400Hz nominal) 0.01Hz ±0.01Hz
Dips & Swells
Vrms1/2 0 ~ 200% of nominal voltage 0.01Vrms ±0.2%
Arms1/2 depends on current clamps 0.01A ±1%
Harmonic (IEC61000-4-7)
Harmonic Number 1 ~ 100(50/60Hz) (IEC61000-4-7) 1~12(400Hz)
Harmonic Voltage %f 0.0 ~ 100.0% 0.01% ±0.1% ± nx0.1%
Harmonic Current %f 0.0 ~ 100.0% 0.01% ±0.1% ± nx0.1%
THD 0.0 ~ 100.0% 0.01% ±2.5%
Phase -180° ~180° 0.1° ± nx0.1°
Power and Energy
P, S, Q1 Max. 6000MW 0.1kW ±1%±10 digits
PF & cosФ 0 ~ 1 0.01 ±0.01
kWh, kVAh, kvarh depends on nominal voltage and current clamps ±1%±10 digits
Flicker (IEC61000-4-15)
Pst(10min)/Plt (2 hrs) 0.00 ~ 20.00 0.01 ±5%
Unbalance
Voltage 0.0 ~ 20.0% 0.10% ±0.1%
Current 0.0 ~ 20.0% 0.10% ±1%
Voltage Phase -360° ~ 0° 0.1° ±0.1°
Current Phase -360° ~ 0° 0.1° ±0.5°
Voltage Transient
Vpk ±6000Vpk 0.01V ±15%
Vrms 10 ~ 1000Vrms 0.01V ±2.5%
Min. Test Time 5us
Inrush Current
Arms depends on current clamps 0.01A ±1% ± 5digits
Inrush Duration 1 ~ 32min selectable 10ms ±20ms
Mains Signaling
Signaling Frequency 60-3000Hz 0.1Hz  
Relative V% 0%-100% 0.10% ±0.4%
Absolute V3s (3s average) 0.0-1000V 0.1V ±5% of Nominal voltage
Logger
Recording user-defined parameters for 4 phases at the same time
Memory Data stored in Micro SD card, 32GB
Duration Time 2 hrs to 1 year, depends on the recording items and time interval
Interval 1s to 60 minutes
Monitor
Support EN50160 in default or user-defined standard